SDCT23D

SPD-Type 2+3

Type 2+3, Single Phase Surge Device ideal for domestic installations

Din rail mountable

Fully Compliant to BSEN61642-11, BSEN62305 & BS7671

Can be used on all Installation Types


Please Click on Image to Enlarge It



Technical Data


SDT23C4P technical data

Click HERE to Download Technical Data PDF



Installation Instruction


According to lightning protection zones concept, for installation at LPZ 0, -1 or higher. This surge protective device is usually installed in distribution-box or feeder bus of UPS, protecting devices or equipment downstream.

Fuse must be installed at the upstream of the SPD or the lightning arrester to make sure that the protected system has double protection. The value of the fuse used in a SPD system should be conformed to:

  1. The value of FUSE should not be larger than the max. withstand capacity of the SPD's backup fuse value.
  2. Under the status of the max. current in the power supply & close loop circuit available current, the fuse should be able to disconnect when overloaded or short-circuited.
  3. Take 1 & 2 into consideration, the fuse should be as large as possible to allow the maximum surge discharge of SPD.


SDT23D installation diagram


SDT23D installation diagram

Click HERE to Download Installation Diagram PDF



Installation Steps


  1. Check the product for integrity of the package; make sure the product window will not indicate red.
  2. Mount the SPD on the 35 mm DIN rail.
  3. Connect conductors, the cross-section area of cable must be larger than 6mm2. The withstand voltage value of cable is not smaller than AC500V; ensure wiring reliable.
  4. If need remote alarm, it should be connected signal lines to remote signal terminal 2 and 3 (When normal, 1 and 3 close, 2 and 3 open; when fault, the state is reversed).
  5. After above, switch on the power supply and turn on the circuit breaker, if the SPD's window indicates green, this indicates the unit is operating normally.

Regularly inspect the operating status, especially after lightning. Once the fuse upstream breaks, or the SPD's window indicates red, electrician should check/replace the SPD.