SDDC1000T2

SPD-Type 2

High Discharge Capacity, Quick Response, Pluggable

Approved fault resistant U circuit, consist of two varistors and thermal disconnection devices

Double thermal disconnection devices, provide more reliable protection


Please Click on Image to Enlarge It



Technical Data


SDDC1000T2 technical data

Click HERE to Download Technical Data PDF



Installation Instruction


This surge protective device is usually installed in DC circuit distribution-box, protecting PV system devices in photovoltaic generator circuit.

Fuse must be installed at the upstream of the SPD or the lightning arrester to make sure that the protected system has double protection. The value of the fuse used in a SPD system should be conformed to:

  1. The value of FUSE should not be larger than the max. withstand capacity of the SPD's backup fuse value.
  2. Under the status of the max. current in the power supply & close loop circuit available current, the fuse should be able to disconnect when overloaded or short-circuited.
  3. Take 1 & 2 into consideration, the fuse should be as large as possible to allow the maximum surge discharge of SPD.


SDDC1000T2 installation diagram


sddc1000t2 installation diagram

Click HERE to Download Installation Diagram PDF



Installation Steps


  1. Check the product for integrity of the package; make sure the product window indicate green.
  2. Mount the SPD on 35 mm DIN rail.
  3. Connect conductors, the cross-sectional area of cable must be larger than 6mm2. The withstand voltage value of cable is not smaller than AC1060V; ensure wiring reliable.
  4. If need remote alarm, it should be connected signal lines to remote signal terminal 1 and 2, or 2 and 3 (When normal, 1 and 2 open, 2 and 3 close; when fault, the state is reversed).
  5. After above, switch on the power supply and turn on the circuit breaker, if the SPD appeared green window, indicates the unit is operating normally.

Regularly inspect the operating status, especially after lightning. Once the fuse upstream break, or the SPD's window not indicate green, electrician should check/replace the SPD.